Inspection, Testing, and Maintenance (IIAR 6, Part 6)

ANSI/IIAR 6-2019 §5.1 lays out the foundational requirements of an ITM Program. Most obligations in this section build upon an existing MI requirement in the PSM regulations (Title 8 CCR §5189(j) and Title 29 CFR §1910.119(j)).

For example, ANSI/IIAR 6-2019 §5.1 requires that “The owner or owner’s designated representative shall ensure an inspection, testing, and maintenance program is developed to reduce the probability of an ammonia release.” This language carries much of the same intent as Title 8 §5189(j)(1)(A) which states that “The employer shall establish and implement written procedures to maintain the ongoing integrity of process equipment and appurtenances.”

Similarly, §5.1.1.1 requires the frequency of inspections and tests to be “consistent with applicable manufacturers’ recommendations and operating history” which parallels the PSM requirement in Title 8 §5189(j)(2)(C). §5.1.1.2 prescribes that inspection and testing procedures follow RAGAGEP which is also required in Title 8 §5189(j)(2)(B).

As it relates to documenting inspections and tests, IIAR 6 requirements extend far beyond PSM as demonstrated in the table below:

IIAR 6 Documentation Requirements
ANSI/IIAR 6-2019 §5.1.1.3
PSM MI Documentation Requirements
Title 8 CCR §5189(j)(2)(D)
Date of the inspection or test Date of Inspection
Name of the individual or individuals who performed the inspection or test Name of person who performed inspection or test
Serial number or other identifier of the equipment on which the inspection or test was performed Serial number or other identifier
Description of the inspection or test performed
Recommended corrective action(s) for each deficiency identified
Description of corrective action(s) for each deficiency identified
Identification of each designated responsible person assigned and authorized to remedy each deficiency identified
Results based on the conditions at commencement of the inspection or test, including instrumentation readings
Expected activation set points (+/-) including a functional description of the control logic
Results based on the conditions after completion of the inspection or test, including instrumentation readings
Expected completion date(s)
Actual completion date(s)

 

Therefore, to comply with IIAR 6, it is probable that the forms you are currently using to document MI tasks may require modification to align with the requirements of IIAR 6.


This is Part 6 of a series on IIAR 6. You can access previous blogs in this series below:

2 responses to “Inspection, Testing, and Maintenance (IIAR 6, Part 6)”

  1. Logan Fitzgerald says:

    Hello,

    Is there any information pertaining to how long we must keep Preventative Maintenance records according to IIAR-6.

    Thank you,

    • Peter Thomas says:

      Yes. ANSI/IIAR 6-2019 §5.3.7 addresses “Retention of Records”. Here are the requirements in Table 5.3.7:

      Daily Inspection Records – Most current 12 months
      Daily Testing Records – Most current 12 months
      Daily Maintenance Records – Most current 12 months
      Annual Inspection Records – Most current 5 years
      Annual Testing Records – Most current 5 years
      Annual Maintenance Records – Most current 5 years
      Five Year Inspection Records – Two (2) most current
      Five Year Testing Records – Two (2) most current
      Five Year Maintenance Records – Two (2) most current
      Ten Year Maintenance Records – Two (2) most current
      Engineering design documentation – Life of the process
      Pressure vessel U1, U-1A, U-3, UM reports – Equipment life
      Log (Operator Transfer of Information) – Most current 12 months
      Secondary Coolant Records – Most current 12 months
      Ammonia Refrigerant Records – Most current 5 years
      Refrigeration Oil Records – Most current 5 years
      Lubrication Records – Most current 5 years
      Pressure Relief Valve (PRV) Records – PRV life
      Current System Records listed in Section 5.3.3 – Life of the process
      Instrument and device testing and calibration – Most current 5 years

Leave a Reply

Your email address will not be published. Required fields are marked *