Question: What is the proper procedure for selecting the pressure relief valve capacity for a positive displacement compressor? Answer: ANSI/IIAR 2-2008 Addendum B §6.1.2.1 addresses this very question. Furthermore, Appendix E (Informative) of that same document gives a detailed example of one acceptable method for determining the proper capacity. A summary of the steps in Appendix […]
Question: Are pressure relief valves required to be installed on an evaporative condenser? Answer: This is a very good question and one that gets asked frequently. Since an evaporative condenser is not a pressure vessel, it is not a black and white requirement as it is for the vessels throughout a refrigeration system. However, the condenser has […]
Here are some excerpts from the most important ammonia stories over the past week… An Ammonia Fueled Car From South Korea – South Korean researchers have successfully road-tested a dual fuel passenger car that runs on a mixture of ammonia and gasoline. It is called the AmVeh and was developed by members of the Ammonia Research […]
On June 21, 2013, Hansen issued a product recall on the following pressure relief valve models with serial numbers between 02B11 and 04B13: Hansen H5600A, H5601, H5602, H5600R, H5602R, and H5632R. These pressure relief valves (sold from February 16, 2011 to April 4, 2013) appear to be more susceptible to internal corrosion when exposed to standing water inside […]
Question: Is it permissible to use galvanized pipe on pressure relief valve discharge piping? Answer: As a “best practice” we recommend using the same piping materials for the closed circuit refrigeration system as for the relief valve discharge piping. Specifically, IIAR-2 states that piping in the closed circuit portion of the system should be of […]