Recent Blog Posts

Pipe Wall Thickness

November 14th, 2017

Pipes are one of the areas of an ammonia refrigeration system most vulnerable to leak. Systems often have hundreds, or even thousands of feet of ammonia pipes serving a variety of purposes. Historically, IIAR Bulletin No. 110 has been the RAGAGEP which governs ammonia pipe inspections and maintenance. §6.7.1 requires that: All uninsulated piping and […]

Pipe Bending

April 27th, 2015

During a recent Mechanical Integrity Inspection, I ran across a pipe that had been bent to facilitate proper joining during installation. My instinct was to view the bent pipe as a Mechanical Integrity deficiency. After reviewing the most current Refrigeration Piping Code (ASME B31.5 §529) I learned that pipe bending is allowed within the limitations defined in the code. Here’s […]