Pipe Plugs and Caps in Ammonia Refrigeration Systems

September 16th, 2025

Question: Are oil drain valves and service valves required to be plugged or capped when not in use? Answer: Yes. All shut-off valves connecting equipment or piping to the atmosphere must be plugged, capped, blanked, or locked closed when they are not in use. ANSI/IIAR 2-2021 §13.3.2.6 states “Shut-off valves connecting ammonia-containing equipment or piping […]

Ammonia Refrigeration System Oil Draining Requirements

October 29th, 2024

Ammonia refrigeration systems must be equipped with a means of draining oil from the system. Over time, small amounts of oil are carried out of the compressors and mix with the ammonia vapor. The ideal place to collect and drain this oil is on the low pressure side of the refrigeration system. The cold temperatures […]